Home / Health, safety, environment & quality
Health, safety, environment & quality
HSE officer: Eng. Mohammed Al-Husseini (OSHA). QA/QC by our sister company Nexana Global.
25,000+safe man-hours
0lost-time injuries since 2023
OSHAcertified HSE officer
ITPinspection & test plan for each activity
Safety
- Risk assessment before each activity; permits to work for hot work and work at height.
- Daily toolbox talks on site and PPE for every worker.
- Segregated work zones in live hospitals and an emergency plan for every site.
Quality control
- Material approval before ordering and inspection on delivery.
- An inspection & test plan (ITP) for each activity, with hold points.
- Pressure, flow, fire-fighting and HVAC system tests before handover.
- QA/QC by our sister company Nexana Global, to the Saudi Building Code and manufacturer guidance.
Material approval before delivery
- Material Approval Request (MAR): datasheet, test certificates, origin, warranty
- Sample checked against the specification and BOQ
- Consultant or owner approval before the purchase order
- Inspection on delivery against the approved sample
- Reject non-conforming material and log it in the NCR register
Inspection & test plan (ITP)
| Activity | Check / test | Acceptance | Point |
|---|---|---|---|
| Concrete | Formwork & rebar before pouring; slump & cube tests | Saudi Building Code SBC 304 | H |
| Waterproofing | Substrate, primer, laps; flood test | Laps ≥ 10 cm · 24–48 h flood test | H |
| Thermal insulation | Board thickness, density and fixing | Per approved material | W |
| HVAC ducts | Leakage test; air balancing (TAB) | SMACNA · airflow within ±10% of design | H |
| Isolation rooms | Negative pressure, air changes | ≥ 2.5 Pa · ≥ 12 ACH (ASHRAE 170) | H |
| Fire-fighting | Hydrostatic pressure test | 200 psi · 2 h · no drop (NFPA 13) | H |
| Plumbing & drainage | Pipe pressure; drainage leak test | Per specification | W |
| Electrical | Insulation resistance, continuity, earthing | Saudi Building Code SBC 401 | H |
| Finishes | Level; paint and epoxy thickness | Per manufacturer | W |
| Handover | Snags, as-built drawings, O&M manuals, warranties | All snags closed | H |
H Hold point: work stops until the consultant or owner signs. W Witness point: the client is notified. Each project's specification overrides these values.
That is our promise to you: to earn your trust on the first project, so it becomes the start of what follows.
Eng. Raed bin Hashem Noor – Owner & General Manager
Thank you, we have received your request and our engineering team will contact you soon.
Your request could not be sent. Please try again or contact us on WhatsApp.